IntelliKnight 5808 Installation Manual 151274-L8
5-7
5.8 Addressing SD Devices
This section tells how to address detectors and modules.
5.8.1 SD505-APS, SD505-AHS, & SD505-AIS
The SD505-APS photoelectric smoke detector, SD505-AHS heat detector, and SD505-AIS ionization smoke
detector are easily addressed at the FACP. The Installer Code is required to perform this task.
To address a SD505-APS, SD505-AHS, or SD505-AIS:
1. Connect a detector base temporarily to the programming terminals as shown in
Figure 5-7. (You can use the same base for each detector).
Figure 5-7 Temporary Connection of Detector Base to Panel for Addressing
2. Enter the Installer code, then press
ENTER.
3. Select 2 for Point Functions.
4. Select 3 for Set SLC Dev Addr.
5. Select “Yes” by pressing the up arrow, then press
ENTER. (The panel will go into trouble at this point. You
can use the SILENCE key to stop the PZT. The trouble will clear automatically when the panel reinitializes
when you finish programming.)
6. When the wait message clears, the following options display:
1- for Read Address. Use to read (or check) a single detectors address.
2 - for Write Address. Use to program a single detectors address.
3 - for Seq. Programming. Use to program more than one detector in sequential order.
7. If you are changing addresses, write the programmed address on the back of the device.
8. To exit press left arrow until fully exited.