Silentknight 5808 User Manual Page 157

  • Download
  • Add to my manuals
  • Print
  • Page
    / 180
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 156
Testing and Troubleshooting 151274-L8
10-4
A message similar to the one shown in Figure 10-2 will display.
Figure 10-2 Shut Down Warning
3. Press the or arrow to toggle NO to YES then press
ENTER.
If NO is chosen you will exit back to the Point Function menu.
If Yes is chosen the system will cease normal operation leaving the premise unprotected.
4. Select the SLC loop.
5. Enter up to eight SLC addresses for the devices you wish to locate.
The LEDs on the selected devices will start flashing.
6. Press to exit SLC multi-locator function.
Note: Once you exit the system will resume normal operation.
10.3.3 I/O Point Control
This feature allows you to toggle any output on or off and trip any input device. This can be useful to test a
point’s output mapping.
Follow these steps to control a I/O point:
1. Select 2 (Point Functions) from the Main Menu.
2. Select 6 (I/O Point Control).
3. Select the Module the point is on.
4. Enter the point number, or press the or arrow to select the point you wish to test, then press
ENTER.
5. Press
ENTER to generate an alarm for an input point or activate an output point.
6. To exit press .
Page view 156
1 2 ... 152 153 154 155 156 157 158 159 160 161 162 ... 179 180

Comments to this Manuals

No comments