7-32
7.7 JumpStart Autoprogramming
To run JumpStart:
1. Enter the installer code.
2. Select 7 for Program Menu.
3. Select 6 for System Options.
4. Press the or arrow to select “Yes” from the warning screen.
5. Press
ENTER.
7.8 Computer Account
An installer at the panel site can initiate communications between the panel and a computer running the 5660
SKSS (see also Section 8.5.19). In order for this communication to function properly both the computer (running
the software) and the control panel must have matching computer account numbers and computer access codes.
Before you program in this location you should know how your control panel will communicate with the
downloading computer, either through direct connect (RS232 or USB) or via the phone lines (Internal Modem).
If the panel initiates the call to a downloading computer, a phone number must be programmed in the computer
accounts area. If the computer initiates the call then answering machine bypass (see Section 7.6.2.6) may need to
be selected.
To program computer account information:
1. Enter the installer code.
2. Select 7 for Program Menu.
3. Select 7 for System Options.
4. Enter the computer account number, then press
ENTER.
5. Enter the computer code (up to 7-digits), then press
ENTER.
6. Enter the phone number the panel will dial to connect to a downloading computer (up to 24-digits), then
press
ENTER. See Table 7-7 for special dialing characters.
7.9 Access Codes
Access codes provide the user access to the control panel functions. Each access code can be customized for each
user. This allows some users the ability to access programming and other higher level panel functions, while
other users may only need access to lower level functions such as preforming fire drills, or acknowledging
trouble conditions.
Profile 1 is the profile that dictates what functions the Fire Fighter Key has access to. Because this is the profile
for a key the user name and the access code can not be edited for this profile.
Profile 2 is the profile for the installer and is referred to as the “Installer Code”. This profile’s user name and
panel functions can not be edited.
IMPORTANT!
JumpStart is intended to be used prior to performing any custom programming. Each time JumpStart is
executed, all options will be reset to their default values. Do not run JumpStart after you have configured
the system through programming.