151274-L8
4-1
Section 4
Control Panel Installation
4.1 Mounting the Control Panel Cabinet
Read the environmental specifications in Section 3.2 before mounting the 5808 panel.
The 5808 cabinet dimensions are:
16" W x 26.4" H x 3.5" D (40.64 cm W x 67.06 cm H x 8.89 cm D).
The 5808 panel should be located within a secured area, where it is accessible to main drop wiring runs and
where it can be easily tested and serviced. End-users responsible for maintaining the panel should be able to hear
alarms and troubles. When selecting a location, keep in mind that the panel itself is the main source of alarm and
trouble annunciation.
When mounting on interior walls, use appropriate screw anchors in plaster. When mounting on concrete,
especially when moisture is expected, attach a piece of 3/4 inch plywood to the concrete surface and then attach
the 5808 to the plywood. Also mount any other desired components to the plywood.
DO NOT flush-mount the 5808 cabinet in a wall designated as a fire break.
4.1.1 Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet through the conduits. Conduits
that are installed to enter the top of the cabinet are most likely to cause water problems. Installers should take
reasonable precautions to prevent water from entering the cabinet. Water damage is not covered under warranty.
4.1.2 Removing the 5808 Assembly from the Housing
If it should ever be necessary to remove the control panel assembly from the cabinet for repair, do so by
removing the screws that hold the control panel in to the cabinet. Do not attempt to disassemble the circuit
boards.
Caution!
To avoid the risk of electrical shock and damage to the unit, power should be OFF at the control panel while