151274-L8
9-1
Section 9
Reporting
This section lists receivers that are compatible with this control panel and the reporting codes sent by the control
panel for SIA and Contact ID formats.
9.1 Receivers Compatible with the Control Panel
The below table shows receivers compatible with the control panel.
9.2 Reporting Formats Table
Manufacturer Model Format
Silent Knight Model 9800 SIA and Contact ID
Model 9000 (SIA formats) SIA
Ademco Model 685 (Contact ID ) Contact ID
Sur-Gard SG-MLR2-DG (V. 1.64 or higher) SIA and Contact ID
Osborne Hoffman Quickalert SIA and Contact ID
SIA Reporting Format Contact ID Reporting Format
Event Description
Event
Family
Module
ID #
(if any)
SIA
Event
Code
Parameter (if
any)
Qualifier
Event
Code
Group
#
Contact
#
System Events
Note: System events are reported when either “Report by Point” or “Report by
Zone” is selected.
AC Power restore Trouble AR 0 3 301 00 000
AC Power lost Trouble AT 0 1 301 00 000
Auto dialer test communication
trouble
Trouble YC Line # 1 350 00 Line #
Auto dialer test communication
trouble restore
Trouble YK Line # 3 350 00 Line #
Battery Voltage restore Trouble YR Exp. ID 3 302 00 Exp. ID
Battery Voltage low Trouble YT Exp. ID 1 302 00 Exp. ID
Ground Fault condition detected Trouble YP Exp. ID 1 310 00 Exp. ID
Emergency Reset
1
Reset OR 1 1 401 00 001
Emergency System Overridden
1
Trouble QS 0 1 244 00 000
Emergency System Overridden
Restore
1
Trouble QR 0 3 244 00 000
Fire System Overridden
1
Trouble FS 0 1 245 00 000
Fire System Override Restore
1
Trouble FR 0 3 245 00 000
Ground fault condition restore Trouble YQ Exp. ID 3 310 00 Exp. ID
Fire Drill has begun Test FI 0 1 604 00 000
Fire Drill ended Test FK 0 3 604 00 000