Installation andOperations ManualINTELLIKNIGHT®MODEL 5808Addressable Fire Control PanelDocument 151274-L810/30/14 Rev: VP/N 151274-L8:V E
IntelliKnight 5808 Installation Manual 151274-L81-21.2 About this ManualThis manual is intended to be a complete reference for all installation and op
Programming 151274-L87-87.3.1.4 Cadence PatternsThe cadence patterns shown in Figure 7-6 are available for use with the control panel. Cadence pattern
IntelliKnight 5808 Installation Manual 151274-L87-97.3.1.5 Zone Accessory OptionsThis option applies to detectors that are used with Sounder bases or
Programming 151274-L87-107.4 GroupAn output group is made up of output points that have been programmed to respond in the same way. Output groups simp
IntelliKnight 5808 Installation Manual 151274-L87-11• Operation with system switches.Figure 7-9 Group Properties Screen Programming OptionsLatching /
Programming 151274-L87-123. To get to this menu item repeat steps 1 through 6 of section 7.4.1.4. To edit group properties, press 2.5. Press the or
IntelliKnight 5808 Installation Manual 151274-L87-13A warning screen will display. If you want to proceed with deleting the group, select Yes. To canc
Programming 151274-L87-145. Select output group number. See Figure 7-10.Figure 7-10 Output Group Template Programming Screen7.5 PointYou may need to
IntelliKnight 5808 Installation Manual 151274-L87-158. Select the function of the device by pressing the or arrows. Refer to Table 7-5 under colum
Programming 151274-L87-16SLC LoopCO SMOKE DETECTORALRM CO/ALRM FIRESUP CO/ALRM FIREALRM CO/SUP FIRESUP CO/SUP FIRELatching Supervisory switches can be
IntelliKnight 5808 Installation Manual 151274-L87-17SLC(cont.)SWITCH(cont.)PAS_ACK Positive acknowledge switch. This switch must be used in zones prog
Introduction 151274-L81-31.3 Compatible ProductsThe chart below lists the products available from Silent Knight for use with the 5808.Note: 5865-3, 58
Programming 151274-L87-187.5.2 Point Programming For Internal or External Power ModuleTo program for an internal or external power module points, foll
IntelliKnight 5808 Installation Manual 151274-L87-1910. Repeat Steps 1 through 15 for all circuits.Table 7-6 Menu Choices for Internal/External Power
Programming 151274-L87-207.5.3 Point Programming For 5880 and 5865 ModulesTo program 5880 or 5865 module points:1. Enter the installer code.2. Select
IntelliKnight 5808 Installation Manual 151274-L87-215. Select the characters for the point name by pressing the or arrow until the desired charact
Programming 151274-L87-22Select Account (ID)The control panel provides up to 4 reporting accounts. The priority of an account is based on its account
IntelliKnight 5808 Installation Manual 151274-L87-23account. Range is 3-5.11. Enter the number of switch attempts (or press the or arrow), then pr
Programming 151274-L87-243. From the Program Menu, select 5 for System Options.4. Select 1 for the phone lines menu.5. Select the phone line to be edi
IntelliKnight 5808 Installation Manual 151274-L87-257.6.2.4 Rotary Format9. Press the or arrow to select the pulse ratio for rotary dialing option
Programming 151274-L87-26Figure 7-16 System Trouble Event Mapping Example7.6.3.2 System Alarm CadenceFire drill and system auxiliary alarm events can
IntelliKnight 5808 Installation Manual 151274-L87-276. Select the holiday schedules you wish to edit (1- holidays 1 - 9, 2- holidays 10 - 18).Figure 7
IntelliKnight 5808 Installation Manual 151274-L81-4The following modems have been tested by Silent Knight for compatibility with the 5808 and the Sile
Programming 151274-L87-286. Enter the desired number of seconds for the alarm verification time. 7. Press or ENTER to make your selection and move to
IntelliKnight 5808 Installation Manual 151274-L87-29Note: The “SYNC Strbs w/ Sil:” only functions with outputs that use a synchronized output pattern.
Programming 151274-L87-30revert to standard time on the last Sunday in October at 2:00 a.m. After January 2007, if this feature is enabled, the system
IntelliKnight 5808 Installation Manual 151274-L87-31A screen similar to the one shown in Figure 7-21 will display. Figure 7-21 Intern
Programming 151274-L87-327.7 JumpStart AutoprogrammingTo run JumpStart:1. Enter the installer code.2. Select 7 for Program Menu.3. Select 6 for System
IntelliKnight 5808 Installation Manual 151274-L87-33Table 7-8 lists the panel functions that can be selected for each user profile. To change an a
Programming 151274-L87-34Note: Profile 1 (Fire Fighter’s Key) the user name and access code can not be edited. Profile 2 (Installer) the user name and
151274-L88-1Section 8System OperationOperation of the control panel is simple. Menus guide you step-by-step through operations. This section of the ma
System Operation 151274-L88-28.2.1 LCD DisplaysThe control panel LCD displays system messages, annunciates alarms, supervisories and troubles; provide
IntelliKnight 5808 Installation Manual 151274-L88-38.4 Menu SystemThe control panel is easy to operate from Main Menu. To view the Main Menu press the
Introduction 151274-L81-5falsely alarm. If the location of a smoke detector causes an abundance of false alarms or nuisance alarms, do not disconnect
System Operation 151274-L88-48.4.2 Using the Menus8.5 Basic Operation8.5.1 Setting Time and Date1. From the Main Menu, select 4 for Set Date and Time.
IntelliKnight 5808 Installation Manual 151274-L88-53. Select 7 for Disable/Enable Pt.4. Use and to move through the list. Press ENTER to select th
System Operation 151274-L88-68.5.10 Conduct a Walk Test1. From the Main Menu, press 1 for System Tests.2. Select 3 for Walk Test-No Rpt. Enter the tim
IntelliKnight 5808 Installation Manual 151274-L88-78.5.14 Check Detector Sensitivity Through Point StatusThe control panel constantly monitors smoke d
System Operation 151274-L88-88.5.15 View Status of a Point1. From the Main Menu, select 2 for Point Status. 2. From the list that displays, press ENTE
IntelliKnight 5808 Installation Manual 151274-L88-93. If you are using the panel’s internal modem to communicate, you will be prompted to enter a phon
System Operation 151274-L88-10Note: Detector status can also be viewed and printed using the 5660 or 5670 (facility monitoring only) SKSS.8.6 Operatio
IntelliKnight 5808 Installation Manual 151274-L88-11AlarmA smoke detector goes into alarm or a pull station is activated.CO detector goes into alarm.I
System Operation 151274-L88-12SupervisoryThe system detects a supervisory condition.The system detects a supervisory condition with a CO detector.The
IntelliKnight 5808 Installation Manual 151274-L88-13TroubleA system trouble condition occurs.A trouble condition with a CO detectorThe dialer seizes c
IntelliKnight 5808 Installation Manual 151274-L81-6• Smoke Detectors shall be installed in sleeping rooms in new construction and it is recommended th
System Operation 151274-L88-14Reset The RESET button is pressed followed by a valid code or rotation of the key.All LEDs are on briefly then the LCD d
IntelliKnight 5808 Installation Manual 151274-L88-158.7 Releasing OperationsThis control panel supports two types of releasing: Double Interlock Zone
System Operation 151274-L88-168.7.1 Single Interlock Zone ReleasingA single interlock zone utilizes a minimum of two addressable detectors, and a desi
IntelliKnight 5808 Installation Manual 151274-L88-178.7.2 Double Interlock Zone ReleasingA Double Interlock Zone uses a minimum of two Addressable det
System Operation 151274-L88-188.8 Smoke Alarm VerificationFigure 8-6 illustrates how the Smoke Alarm Verification cycle operates.Figure 8-6 Smoke Ver
151274-L89-1Section 9ReportingThis section lists receivers that are compatible with this control panel and the reporting codes sent by the control pan
Reporting 151274-L89-2Initial Power up Trouble RR 0 1 305 00 000Local Programming begin Trouble LB 0 1 627 00 000Local Programming ended normally Trou
IntelliKnight 5808 Installation Manual 151274-L89-3Voice VBUS Trouble1Trouble ET Exp. ID 1 332 00 Exp. IDVoice VBUS Trouble Restore1Trouble ER Exp. ID
Reporting 151274-L89-4Water release circuit has been disabledTrouble pi Exp. ID SS Point # 1 203 Exp. ID Point #Water release circuit has been re-enab
IntelliKnight 5808 Installation Manual 151274-L89-5Notification Trouble Trouble FT 1000+Group #1 320 00 Group #Notification Output trouble restore Tro
151274-L82-1Section 2Agency Listings, Approvals, and Requirements2.1 Federal Communications Commission (FCC)The following information must be provided
Reporting 151274-L89-6Zone-based AUX1 switch trouble restoreTrouble UJ 1000+ Zone # 3 373 01 Zone #Zone-based AUX2 switch trouble restoreTrouble UJ 20
IntelliKnight 5808 Installation Manual 151274-L89-7Emergency NAC Trouble Restored1Trouble pi Exp. ID QJ Point # 3 320 Exp. ID Point #Emergency Control
Reporting 151274-L89-8Positive Alarm sequence acknowledge switch troubleTrouble pi Exp. ID FT Point # 1 373 Exp. ID Point #Point Enabled Disable pi Ex
IntelliKnight 5808 Installation Manual 151274-L89-9Voice Aux Status Switch Disabled1Disable pi Exp. ID UB Point # 1 580 Exp. ID Point #Voice Aux Statu
151274-L810-1Section 10Testing and Troubleshooting10.1 TroubleshootingThis section of the manual offers suggestions for troubleshooting hardware probl
Testing and Troubleshooting 151274-L810-210.2.1 Periodic Testing and MaintenanceTo ensure proper and reliable operation, it is recommended that system
IntelliKnight 5808 Installation Manual 151274-L810-310.2.2 Event HistoryThe event history can be useful for tracking or recalling a trouble condition.
Testing and Troubleshooting 151274-L810-4A message similar to the one shown in Figure 10-2 will display.Figure 10-2 Shut Down Warning3. Press the o
IntelliKnight 5808 Installation Manual 151274-L810-510.4 Impedances that Cause Earth Ground FaultsTable 10-1 show the minimum impedances that cause an
151274-L811-1Section 11Installation RecordsThis section of the manual is for you to use if you wish to track of how points, zones, and groups have bee
Agency Listings, Approvals, and Requirements 151274-L82-2installer.2.2 Underwriters Laboratories (UL)2.2.1 Requirements for All InstallationsGeneral r
Installation Records 151274-L811-2On-board 61 On-board 95On-board 62 On-board 96On-board 63 On-board 97On-board 64 On-board 98On-board 65 On-board 99O
151274-L8A-1Appendix ACompatible DevicesA.1 Notification AppliancesFor proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL
Compatible Devices 151274-L8A-2Faraday446 Vibrating Bell 476 Vibrating Bell477 Single Stroke Bell2700 -M. -R, -T, -Y, -Z Strobe2701 Series Strobe2705
IntelliKnight 5808 Installation Manual 151274-L8A-3Faraday(cont.)5346 Electronic Horn with Strobe5347 Electronic Horn with Strobe5348 Single Tone Horn
Compatible Devices 151274-L8A-4Faraday(cont.)6300 Mini-Horn6301 Mini-Horn 6302 Mini-Horn6310 Mini-Horn/Strobe6311 Mini-Horn/Strobe6312 Mini-Horn/Strob
IntelliKnight 5808 Installation Manual 151274-L8A-5FCI(cont.)S24110-FC StrobeS24110W-FC StrobeS24110K-FC StrobeFederal Signal450 HornVALS Horn/StrobeG
Compatible Devices 151274-L8A-6Gentex(cont.)WGEC24-75WxxWeatherproof Horn/StrobeWGES24-75WxWeatherproof StrobeWGMS-24-X x x Horn/StrobeSystem SensorCH
IntelliKnight 5808 Installation Manual 151274-L8A-7System Sensor(cont.)PC4Rxx4-Wire Horn/StrobeP4RHxx4-Wire Horn/Strobe High CandelaP4Wxx4-Wire Horn/S
Compatible Devices 151274-L8A-8WheelockAH-12xHornAH-24xHornAH-12WPxHorn WeatherproofAH-24WPxHorn WeatherproofAMT-241575WxxMulti-Tone Horn StrobeAMT-24
IntelliKnight 5808 Installation Manual 151274-L8A-9Wheelock (cont.)MTWPA-2475WxxMultitone Horn StrobeMTWPB-2475WxxMultitone Horn StrobeMTWPG-2475WxxMu
IntelliKnight 5808 Installation Manual 151274-L82-32.2.3 Requirements for Local Protected Fire Alarm SystemsAt least one UL listed supervised notifica
Compatible Devices 151274-L8A-10Wheelock (cont.)RSSWPG-24MCCHxStrobe Weatherproof RSSWPR-24MCCHxStrobe Weatherproof RSSWP-2475WxStrobe Weatherproof RS
IntelliKnight 5808 Installation Manual 151274-L8A-11A.2 Two-Wire Smoke DetectorsTable A-2 lists two-wire smoke detectors that are compatible with the
Compatible Devices 151274-L8A-12ESL 429C (S10A) N/A S10A 30 / loop429CRT (S11A) N/A S11A 30 / loop429CST (S11A) N/A S11A 30 / loop429CT (S10A) N/A S10
IntelliKnight 5808 Installation Manual 151274-L8A-13A.3 Compatible 520Hz Low Frequency BasesSystem Sensor 1400 A N/A 20 / loop1451 (B401B) A A 20 / lo
151274-L8B-1Appendix BSpecial Characters ListsThis section contains tables of programmable characters that may be used for device, module, and zone na
Silent Knight Fire Product Warranty and Return PolicyGeneral Terms and Conditions• All new fire products manufactured by Silent Knight have a limited
Manufacturer Warranties and Limitation of LiabilityManufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that th
Cut Along the Dotted LineP/N 151273-L8 Rev. C Model 5808 Basic Operating InstructionsThese Instructions must be framed and displayed next to th
Cut Along the Dotted Line
151274-L83-1Section 3Before You Begin InstallingThis section of the manual is intended to help you plan your tasks to facilitate a smooth installation
Silent Knight12 Clintonville RoadNorthford, CT 06472-1610203-484-7161Fax: 203-484-7118www.silentknight.com
Before You Begin Installing 151274-L83-23.3 Electrical SpecificationsTable 3-1 list the terminal block on the 5808 as well as a description of the eac
Installation ProcedureInstallation Precautions - Adherence to the following will aid in problem-free installation with long-term reliability: WARNING
IntelliKnight 5808 Installation Manual 151274-L83-33.4 Wiring SpecificationsInduced noise (transfer of electrical energy from one wire to another) can
Before You Begin Installing 151274-L83-43.5 Board Assembly Diagram Figure 3-2 Model 5808 AssemblyFigure 3-2 shows the circuit boards and annunciato
IntelliKnight 5808 Installation Manual 151274-L83-53.6 Calculating Current Draw and Standby BatteryThis section is for helping you determine the curre
Before You Begin Installing 151274-L83-6SK-Photo(99 max.)1Standby/Alarm: .30 mA6mA mASK-Photo-T mA mASK-Ion mA mASK-Heat
IntelliKnight 5808 Installation Manual 151274-L83-7SLC AccessoriesB200SR Sounder Base(99 max.)Aux Pwr Standby: .5 mA mAAlarm:
Before You Begin Installing 151274-L83-81. Total does not include isolator devices or accessory bases.2. If using door holders, you do not need to con
IntelliKnight 5808 Installation Manual 151274-L83-9SD500-LED(40 max.)1Aux. Pwr Standby: 10 mA mAAlarm:
Before You Begin Installing 151274-L83-101. Total does not include isolator devices or accessory bases.2. If using 24 VDC aux power only. No standby o
IntelliKnight 5808 Installation Manual 151274-L83-113.7 Installation Tasks OverviewThis section provides a chart listing tasks that need to be perform
Before You Begin Installing 151274-L83-12Program type of switch (manual pull, fire drill, and so on), if necessary. (JumpStart assigns all switches as
Contents1ContentsSection 1Introduction ...
151274-L84-1Section 4Control Panel Installation4.1 Mounting the Control Panel CabinetRead the environmental specifications in Section 3.2 before mount
Control Panel Installation 151274-L84-24.2 AC ConnectionAt installation, connect the AC terminals to the power source as shown in Figure 4-1. It may b
IntelliKnight 5808 Installation Manual 151274-L84-34.3.1 RBB Accessory CabinetThe Model RBB Accessory cabinet can be used when your backup batteries r
Control Panel Installation 151274-L84-43. Run extended battery cable from control panel cabinet through conduit to RBB cabinet. See Figure 4-5.Figure
IntelliKnight 5808 Installation Manual 151274-L84-54.4 SBUS WiringThis section contains information on calculating SBUS wire distances and the types o
Control Panel Installation 151274-L84-6Note: The following formulas were used to generate the wire distance chart:Wiring Distance calculation example:
IntelliKnight 5808 Installation Manual 151274-L84-74.4.2 Wiring ConfigurationsFigure 4-7 illustrates Class B configuration.Figure 4-7 SBUS Class B Wi
Control Panel Installation 151274-L84-84.5 5860 Remote Annunciator InstallationThe optional Model 5860 Remote Annunciator, shown in Figure 4-8, perfor
IntelliKnight 5808 Installation Manual 151274-L84-94.5.1 Mounting the 5860This section of the manual describes mounting the remote annunciator. The an
Control Panel Installation 151274-L84-10(See Figure 4-10 for location of the set screws.) Figure 4-10 Annunciator Back Box and Bezel Details4
Contents24.3 Battery Connection ...4-2
IntelliKnight 5808 Installation Manual 151274-L84-11annunciator. Studs used with an electrical box must be two by fours (or larger).Figure 4-11 Place
Control Panel Installation 151274-L84-124.5.1.2 Surface MountingThe 5860 can be mounted directly to a surface or can be attached to a single, double,
IntelliKnight 5808 Installation Manual 151274-L84-135. Connect a printer to the 5824 as shown in Figure 4-15. Figure 4-14 5824 Connection to the Pane
Control Panel Installation 151274-L84-14• Select a name, if desired (see Section 7.2.1.1).• Select options for the printer and the output port. See be
IntelliKnight 5808 Installation Manual 151274-L84-15number. Figure 4-17 5880 Board Layout 4.7.2 FACP ConnectionThe 5880 connects to the panel via the
Control Panel Installation 151274-L84-164.7.3 LED WiringThere are four 12-pin connectors on the 5880 board for connecting LEDs. Each LED gets its powe
IntelliKnight 5808 Installation Manual 151274-L84-174.7.4 Dry Contact WiringThe 8 input circuits on the 5880 board are for monitoring switch inputs-an
Control Panel Installation 151274-L84-184.8 5865-3 / 5865-4 LED Annunciator InstallationThe 5865-3 and 5865-4 are LED annunciators. The 5865-4 has 30
IntelliKnight 5808 Installation Manual 151274-L84-194.8.2 5865 MountingMount the 5865-4 to a standard 4-gang electrical box. Mount the 5865-3 to a sta
Control Panel Installation 151274-L84-204.9 Configuring ModulesThis section describes how to configure any system hardware modules that have been adde
Contents35.3 Maximum Number of Devices ...5-25.4 Wirin
IntelliKnight 5808 Installation Manual 151274-L84-214.10 Telephone ConnectionConnect the telephone lines as shown in Figure 4-26. The Model 7860 phone
Control Panel Installation 151274-L84-22Figure 4-27 Class B Notification Appliance Circuit Wiring4.11.1.2 Class A Notification WiringYou must use an
IntelliKnight 5808 Installation Manual 151274-L84-232. Configure the circuit for Class A in programming (see Section 7.5).Figure 4-28 Class A Notific
Control Panel Installation 151274-L84-24power is immediately restored to the door holder circuits. Figure 4-29 Example of an Auxiliary Power For Door
IntelliKnight 5808 Installation Manual 151274-L84-254.12 On-Board Programmable Relays (Conventional)The control panel has two built-in programmable re
Control Panel Installation 151274-L84-264. Program NAC circuit 2 for alarm.5. Program NAC circuit 1 for supervisory non latching.Note: NACs must be pr
IntelliKnight 5808 Installation Manual 151274-L84-27It is not possible to reset the remote indication until you clear the condition and reset the cont
Control Panel Installation 151274-L84-28rent using the potentiometer (R10) on the 5220 board. Normal loop current is 2-to-8 mA with a 1k ohm remote st
IntelliKnight 5808 Installation Manual 151274-L84-294. Program the output group characteristics as non-silenceable and reverse polarity. See Section 7
Control Panel Installation 151274-L84-304.13.4 Using the SD500-ARM Addressable Relay ModuleWhen the SD500-ARM is wired for polarity reversal, it repor
Model 5808 Installation Manual47.3.2 Add Zone ...
IntelliKnight 5808 Installation Manual 151274-L84-314.13.5 Using a MR-201/T Control Relay From Air ProductsWhen the MR-201/T control relay is wired fo
Control Panel Installation 151274-L84-324.13.6 Transmitter Activated by Dry ContactsThis section describes the connection of a UL 864 listed remote st
151274-L85-1Section 5SK and SD SLC Device Installation5.1 List of SK SLC DevicesThe following SK SLC devices can be used with the control panel. See t
SK and SD SLC Device Installation 151274-L85-25.2 List of SD SLC DevicesThe following SD SLC devices can be used with the control panel. See the appro
IntelliKnight 5808 Installation Manual 151274-L85-35.4.1 Wiring SLC in Style 4 (Class B) ConfigurationNo special wire is required for addressable loop
SK and SD SLC Device Installation 151274-L85-4must be met in addition to the maximum distance requirements for the various wire gauges.
IntelliKnight 5808 Installation Manual 151274-L85-5Note: No t-taps allowed on class A SLC loops.5.5 SK Detector InstallationThis section describes how
SK and SD SLC Device Installation 151274-L85-65.6 Addressing SK SLC DevicesAll SK devices are addressed using the two rotary dials that appear on the
IntelliKnight 5808 Installation Manual 151274-L85-75.8 Addressing SD DevicesThis section tells how to address detectors and modules.5.8.1 SD505-APS, S
SK and SD SLC Device Installation 151274-L85-85.8.2 SLC Devices with DIP SwitchesInput and relay module addresses are set using the DIP switches on th
Contents5Section 8System Operation ...
151274-L86-1Section 6Programming OverviewThis section of the manual is intended to give you an overview of the programming process. Please read this s
Programming Overview 151274-L86-21 using constant on output when an alarm condition occurs. Circuit 5 (Relay 1):Assigned to Group 124. JumpStart autom
IntelliKnight 5808 Installation Manual 151274-L86-37. Select one of the following options from the menu that displays. 1 - Review System Press 1 i
Programming Overview 151274-L86-46.2 Mapping OverviewThis section of the manual is an overview of mapping. Details about how to select mapping options
IntelliKnight 5808 Installation Manual 151274-L86-56.2.1 Input Point MappingInput points are assigned to input zones. Any input point can be assigned
Programming Overview 151274-L86-66.2.2 Output Circuit MappingFigure 6-3 is a simple example showing how to assign notification and relay output circui
IntelliKnight 5808 Installation Manual 151274-L86-76.2.3 Zone Event Mapping There are 11 types of events that can occur in zones (see below). For each
Programming Overview 151274-L86-8Figure 6-5 Example of Zone Events Mapped to Output Groups and Patterns
IntelliKnight 5808 Installation Manual 151274-L86-96.2.4 Mapping LED PointsFigure 6-6 is a simple example showing how LED points are mapped to zones a
Programming Overview 151274-L86-106.3 Programming Using the 5660 Silent Knight Software SuiteYou can use the 5660 Silent Knight Software Suite (SKSS)
Model 5808 Installation Manual610.2 Common Problems ...
IntelliKnight 5808 Installation Manual 151274-L86-116.4.2 Moving through the MenusFigure 6-8 shows how to move through Program Menu screens, using the
Programming Overview 151274-L86-126.5 Programming Menu Quick ReferenceThis section of the manual lists all Program Menu options in the order they appe
IntelliKnight 5808 Installation Manual 151274-L86-13Group1Edit Group Select Group to EditGroup Name Section 7.4.1.1Group PropertiesLatching Options*No
Programming Overview 151274-L86-14PointInternal and External 5815XL, SK DevicesSensor Point #UNUSEDSection 7.5.1DETECTORPHOTO, ION, HEAT,ACCLIMATEHEAT
IntelliKnight 5808 Installation Manual 151274-L86-15Point(cont.)Internal and External 5815XL, SK DevicesSensor Point #SUP DETPHOTO, ION, HEAT,ACCLIMAT
Programming Overview 151274-L86-16Point(cont.)Internal and External 5815XL, SK DevicesSensor Point #CO FIREALRM Fire/ALRM CO, ALRM Fire/SUPR CO, SUPR
IntelliKnight 5808 Installation Manual 151274-L86-17Point(cont.)Internal and External 5815XL, SK DevicesModule Point # DETECTOR 2WIRE SMK*Silenceable
Programming Overview 151274-L86-18Point(cont.)Internal and External 5815XL, SD DevicesPoint #SUP DETPHOTO, ION, HEAT*Latching (LA) or Non-Latching (NL
IntelliKnight 5808 Installation Manual 151274-L86-19Point(cont.)Internal and External 5815XL, SD DevicesPoint #SWITCHFIREDRILL, SILENCE, RESET*Silence
Programming Overview 151274-L86-20Point(cont.)Internal and External Power SupplyPoint #B SWITCHFIREDRILL, SILENCE, RESET*Silenceable (SI) or Non-Silen
151274-L81-1Section 1IntroductionThe 5808 Fire Alarm Control / Communicator is an addressable fire control system that meets the requirements of UL 86
IntelliKnight 5808 Installation Manual 151274-L86-21Point(cont.)5880Point #SWITCHSYS_AUX1, SUS_AUX2*Latching (LA) or Non-Latching (NL)Section 7.5.3*Si
Programming Overview 151274-L86-22System OptionsSystem Event OutputsTrouble EventsSystem TroubleSelect Group (*None)Section 7.6.3.1Select Cadence (*No
IntelliKnight 5808 Installation Manual 151274-L86-23System Options(cont.)Daylight SavingsDST*Y (Enabled) or N (Disabled)Automatic Daylight Saving Time
151274-L87-1Section 7ProgrammingThis section of the manual describes how to manually program the control panel from the built-in annunciator. Each sub
Programming 151274-L87-27.2.1 Edit ModulesThe features that can be edited when this option is selected are, module name, and class of wiring (Class A
IntelliKnight 5808 Installation Manual 151274-L87-32. Press 7 for Program Menu.3. Press 1 to enter module menu.4. Press 2 to add a module.5. From the
Programming 151274-L87-43. Press 2 to enter zone menu.4. Press 1 to edit a zone.5. Enter the zone number, then press ENTER.7.3.1.1 Edit Zone Name6. Pr
IntelliKnight 5808 Installation Manual 151274-L87-5Table 7-1 list the delay choices and a description of each.4. Press ENTER.Heat Temperature SettingU
Programming 151274-L87-67.3.1.3 Zone OutputsOutput groups and cadence patterns are mapped to events. They can be programmed to output when an event oc
IntelliKnight 5808 Installation Manual 151274-L87-7Zone Mapping ExampleSuppose you want to program Zone 1 so that:• Any alarm (detector, water flow or