Model SK-5208 Installation Manual 151204
3-25
3. Mount the SK-5217 onto the standoffs and bracket located in the cabinet. See Figure 3-23.
Figure 3-23 Model SK-5217 Remote Installation
4. Connect the SK-5217 to the SK-5208 control panel as shown in Figure 3-19.
5. Set the ID code (see Section 3.14.1).
If ID code 1 is selected the SK-5217 will input zones 11 - 20.
If ID code 2 is selected the SK-5217 will input zones 21 - 30.
6. Wire the zone inputs to the zone expander as shown in Figure 3-20.
3.14.5 Model 5824 Installation Instructions
The Model 5824 provides the 5208 with the ability to communicate to a serial or parallel printer to print the event
log. You can use one 5824 on the 5208. The 5824 is for ancillary use only.
3.14.5.1 Mounting the 5824 Module
The 5824 comes in a plastic enclosure, follow these steps to mount the 5824’s plastic enclosure:
1. Remove the 5824’s cover. Use a small screw driver if necessary.
Mounting
Holes
Mounting
Holes