Silentknight SK-5208 Conventional FACP 10-30 Zone User Manual Page 1

Browse online or download User Manual for Safety Silentknight SK-5208 Conventional FACP 10-30 Zone. SilentKnight SK-5208 Conventional FACP 10-30 Zone User Manual [en] [pl] [cs]

  • Download
  • Add to my manuals
  • Print
  • Page
    / 102
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
Installation and
Operations Manual
Model
SK-5208
Fire Control / Communicator
Document 151204
05/15/2014 Rev:
M
P/N 151204:M ECN: 14-0068
Page view 0
1 2 3 4 5 6 ... 101 102

Summary of Contents

Page 1 - Operations Manual

Installation andOperations ManualModelSK-5208Fire Control / CommunicatorDocument 15120405/15/2014 Rev: MP/N 151204:M ECN: 14-0068

Page 2 - Installation Procedure

Agency Listings and Requirements

Page 5

Silent Knight12 Clintonville RoadNorthford, CT 06472-1610203-484-7161Fax: 203-484-7118www.silentknight.com

Page 6 - Introduction

1512043-1Section 3Control Panel Installation3.1 Electrical Specifications3.2 Environmental SpecificationsIt is important to protect the SK-5208 contro

Page 7 - 1.3.1 Optional Accessories

Control Panel Installation

Page 8

Model SK-5208 Installation Manual 1512043-33.4 Control Board Components Figure 3-2 is a wiring diagram for wiring the Model SK-5208 panel.Figure 3-2

Page 9 - Section 2

Control Panel Installation

Page 10 - Restricted Options:

Model SK-5208 Installation Manual 1512043-53.6.2 Current Draw WorksheetUse Table 3-2 to determine current requirements during alarm/battery standby op

Page 11 - Control Panel Installation

Control Panel Installation

Page 12

Model SK-5208 Installation Manual 1512043-7Note: Note: All conduit and wiring connected to the SK-5208 must meet the applicable National Electric Cod

Page 13 - 3.4 Control Board Components

Control Panel Installation

Page 14 - 3.6 Current Draw Calculations

Model SK-5208 Installation Manual 1512043-9Remote Annunciator Connections30 SKI Used to connect 5235 remote annunciators to the control panel.31 SKO32

Page 15 - 3.6.2 Current Draw Worksheet

Installation ProcedureAdherence to the following will aid in problem-free installation with long-term reliability:Installation Precautions - Adherence

Page 16 - 3.7 AC Wiring

Control Panel Installation

Page 17 - 3.8 Backup Batteries

Model SK-5208 Installation Manual 1512043-11zones. These zones must be wired using normally open contacts.Figure 3-5 Class A (Style D) Supervised Fir

Page 18

Control Panel Installation

Page 19

Model SK-5208 Installation Manual 1512043-133.11.4 Two-Wire Smoke Detector ConnectionFigure 3-8 shows how to connect two-wire smoke detectors to Class

Page 20 - 3.11 Detector Installation

Control Panel Installation

Page 21

Model SK-5208 Installation Manual 1512043-153.13 Auxiliary RelaysThe SK-5208 provides four programmable auxiliary relay outputs. Relays can be program

Page 22 - Power Limited

Control Panel Installation

Page 23

Model SK-5208 Installation Manual 1512043-172. Secure it to the wall using #6 or #8 screws. The mounting plate should be oriented so that the word TOP

Page 24

Control Panel Installation

Page 25 - 3.14 Accessory Devices

Model SK-5208 Installation Manual 1512043-19- 30, or system status outputs. See Section 4.2.11.Figure 3-14 Model SK-5280 Connection to the Control Pa

Page 26

Contents 1ContentsSection 1Introduction ...

Page 27 - 3.14.2.2 Wiring the SK-5235

Control Panel Installation

Page 28

Model SK-5208 Installation Manual 1512043-21C1 is the coil for the relay 1, C2 is the coil for relay 2, C3 and C4 are the coils for relays 3 and 4 res

Page 29

Control Panel Installation

Page 30 - 3.14.3.2 Wiring Relays

Model SK-5208 Installation Manual 1512043-23Voltage:17.5 to 28 VDCFigure 3-20 Model SK-5217 Two-wire Detectors Figure 3-21 4-Wire Detector Connectio

Page 31 - 2.5A @ 30 VDC/120 VAC

Control Panel Installation

Page 32 - 3.14.4.1 Zone Inputs

Model SK-5208 Installation Manual 1512043-253. Mount the SK-5217 onto the standoffs and bracket located in the cabinet. See Figure 3-23.Figure 3-23 M

Page 33 - Voltage:17.5 to 28 VDC

Control Panel Installation

Page 34

Model SK-5208 Installation Manual 1512043-27Figure 3-25 Model 5824 Serial/Parallel Port, and ID Selector Switch location3.15 Special Applications3.15

Page 35 - Mounting

Control Panel Installation

Page 36

Model SK-5208 Installation Manual 1512043-294. If necessary, adjust circuit current using potentiometer R10 on the 5220 board. Normal circuit current

Page 37 - 3.15 Special Applications

Installation Manual 23.14.2 Model SK-5235 Remote Annunciator ...

Page 38

Control Panel Installation

Page 39

Model SK-5208 Installation Manual 1512043-311. Wire the MR-201/T as shown in Figure 3-29.Figure 3-29 Wiring the MR-201/T2. Program the NAC circuit as

Page 40

1512044-1Section 4 ProgrammingThe SK-5208 control panel can be programmed from either the on-board annunciator or the SK-5235 remote annunciator. You

Page 42 - Programming

Model SK-5208 Installation Manual 1512044-34.2 Programming FlowFigure 4-2 provides an overview of the programming menu flow. Figure 4-3 through Figure

Page 44 - 4.2 Programming Flow

Model SK-5208 Installation Manual 1512044-54.2.2 Misc System OptionFigure 4-4 illustrates, in more detail, the programming flow when in the misc syste

Page 46 - 4.2.2 Misc System Option

Model SK-5208 Installation Manual 1512044-74.2.4 NAC OptionsFigure 4-6 illustrates, in more detail, the programming flow when in the NAC options menu.

Page 48 - 4.2.4 NAC Options

Contents 35.4 LED Indicators ...

Page 49 - 4.2.5 Relay Options

Model SK-5208 Installation Manual 1512044-94.2.6 User CodeFigure 4-8 illustrates, in more detail, the programming flow when in the user code menu.Figu

Page 50 - 4.2.6 User Code

Programming 15120

Page 51 - 4.2.7 Account

Model SK-5208 Installation Manual 1512044-114.2.8 Computer OptionsFigure 4-10 illustrates, in more detail, the programming flow when in the computer o

Page 53 - 4.2.9 Line Options

Model SK-5208 Installation Manual 1512044-134.2.10 Misc ReportingFigure 4-12 illustrates, in more detail, the programming flow when in the miscellaneo

Page 55 - 4.2.11 5280 Outputs

Model SK-5208 Installation Manual 1512044-154.2.12 5824 Expander OptionsFigure 4-14 illustrates, in more detail, the programming flow for the 5824 ser

Page 57 - 4.2.13 DST/Clk Options

Model SK-5208 Installation Manual 1512044-174.3 Programming OptionsTable 4-4 list all the programming options and the items that can be modified withi

Page 60

Model SK-5208 Installation Manual 1512044-19Misc System(cont.)5217 Expanders1 Enables zones 11-20.2 Enables zones 21-30Plex DoorNo X If Yes is selecte

Page 61

Programming 15120

Page 62

Model SK-5208 Installation Manual 1512044-21Account (1-4) #Account <#> #Enter a 6-digits number1: 1052082: 2052083: 3052084: 405208Enter any val

Page 63

Programming 15120

Page 64

Model SK-5208 Installation Manual 1512044-23Misc Reporting*3/1 Alarm0 - 9* Event code for 3/1 and 4/2 reporting formats.0Alarms for Fire, Waterflow, U

Page 65

Programming 15120

Page 66 - Operation

1512045-1Section 5OperationTo operate the SK-5208 you can use either the on-board touchpad or the Model SK-5235 Remote Annunciator.Figure 5-1 Model S

Page 67

Operation 1512045

Page 68 - 5.4 LED Indicators

Model SK-5208 Installation Manual 1512045-3Also displays Firmware number and revision as shown in Figure 5-3.Figure 5-3 Firmware Numbers and Revision

Page 70 - 8210G207 24 VDC, 10.6 W

Model SK-5208 Installation Manual 1512041-2 1.3.1 Optional Accessories Limitations of Fire Alarm SystemsManufacturer recommends that smoke and/or he

Page 71 - 5.6 Smoke Alarm Verification

Model SK-5208 Installation Manual 1512045-5A Model 7641 EOL resistor/diode assembly is required when connecting the FACP to releasing solenoids. The 7

Page 73 - Download Menu Upload Menu

Model SK-5208 Installation Manual 1512045-75.7 System TestingThis section describes operation of fire drills, zone testing, and the 24-hour automatic

Page 74 - Serial Port

Operation 1512045

Page 75 - Reporting

Model SK-5208 Installation Manual 1512045-9you do not select a name for the file, it will be automatically named with the panel model and the date and

Page 76 - 6.2 Reporting Codes

1512046-1Section 6ReportingThe SK-5208 can transmit information in four different formats. This section describes the four basic reporting formats of

Page 77

Reporting 1512046

Page 78

Model SK-5208 Installation Manual 1512046-3Fire Trouble/Clean-Me Trouble 1-30 FT1 - FT30 T1 - T0 Trouble Code 1 373 001 - 1 373 030Fire Unbypass FU1-F

Page 79

Reporting 1512046

Page 80 - Troubleshooting

Model SK-5208 Installation Manual 1512046-56.2.1 Default Settings for 3/1 FormatTable 6-3 displays the default settings which are set in the Misc. Rep

Page 81

Introduction 1512041-3fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessar

Page 82 - 7.3 Earth Fault Resistance

1512047-1Section 7TroubleshootingThis section of the manual contains information that can be used to isolate and correct installation problems encount

Page 84

Model SK-5208 Installation Manual 1512047-37.3 Earth Fault ResistanceTable 7-2 list the earth fault resistance values for each applicable terminal on

Page 85

151204A-1Appendix ACompatible DevicesThis section of the manual lists devices (smoke detectors and notification appliances) that are compatible with t

Page 86

Compatible Devices

Page 87

Model SK-5208 Installation Manual 151204A-3Faraday(cont.)5346 Electronic Horn with Strobe5347 Electronic Horn with Strobe5348 Single Tone Horn/Strobe5

Page 88

Compatible Devices

Page 89

Model SK-5208 Installation Manual 151204A-5FCI(cont.)S24110-FC StrobeS24110W-FC StrobeS24110K-FC StrobeFederal Signal450 HornVALS Horn/StrobeGentexGEC

Page 90

Compatible Devices

Page 91

Model SK-5208 Installation Manual 151204A-7System Sensor(cont.)PC4Rxx4-Wire Horn/StrobeP4RHxx4-Wire Horn/Strobe High CandelaP4Wxx4-Wire Horn/StrobePC4

Page 92 - Smoke Detectors

1512042-1Section 2Agency Listings and RequirementsInstall and maintain in accordance with NFPA 72. Detector spacing shall be in accordance to NFPA 72.

Page 94 - Fire Protec

Model SK-5208 Installation Manual 151204A-9Wheelock (cont.)MTWPA-2475WxxMultitone Horn StrobeMTWPB-2475WxxMultitone Horn StrobeMTWPG-2475WxxMultitone

Page 95

Compatible Devices

Page 96 - System Sensor

Model SK-5208 Installation Manual 151204A-11 A.2 Two-Wire Smoke DetectorsThe table below lists two-wire smoke detectors that are compatible with the S

Page 98

Model SK-5208 Installation Manual 151204A-13HochikiSIH-24F (HS-224D or HSB-224) N/A N/A 25SLK-12 N/A N/A 25SLK-24F (HS-224D) N/A N/A 25SLK-24FH (HS-22

Page 99 - SK-5208 panel in

Compatible Devices

Page 100

1Silent Knight Fire Product Warranty and Return PolicyGeneral Terms and Conditions• All new fire products manufactured by Silent Knight have a limited

Page 101

2Manufacturer Warranties and Limitation of LiabilityManufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that t

Page 102

Cut Along the Dotted LinePN 151214 Rev BECN 14-00Model SK5208 Basic Operating InstructionsThese Instructions must be framed and displayed next to the