SD500-SDM Installation
Instructions
The SD500-SDM two-wire smoke module
allows you to connect a loop of conventional
detectors to a Silent Knight addressable fire
alarm control panel (FACP). Each loop can then
be assigned an address on the FACP.
Specifications
Compatibility
The SD500-SDM is compatible with all Silent
Knight addressable FACPs.
Wiring
Note: Installation and wiring of this device must be done in
accordance with NFPA 72 and local ordinances.
Important! All wiring is supervised and power limited.
Connecting the SD500-SDM
to the SLC Loop
The SD500-SDM connections to the 5815XL
internal and external are the same. Wire as
shown in Figure 1.
Figure 1: SLC Wiring
Smoke Detector Connections
This section contain instructions on how to
connect a 2-wire conventional smoke detector
loop to the SD500-SDM for either Class B (Style
B), or Class A (Style D).
Class B (Style B) Wiring
Wire Class B (Style B) conventional smoke
detector loop to the SD500-SDM as shown in
Figure 2. Place the jumper block in the Class B
Specification Parameter Rating
2-Wire Smoke Detector
Loop Current:
Standby: 2 mA max.
Alarm: 100 mA max.
Operating Voltage: SLC 32 VDC
Aux Power 24 VDC
SLC Current for battery
calculation:
Alarm: .55 mA
Standby: .55 mA
Operating Temperature: 32° - 120° F
(0° - 49° C)
Humidity: 10-85% RH
Max. SLC Loop Resistance: 50 Ω
Max. 2-wire Conventional Smoke Loop
Resistance
50 Ω
Dimensions: Length: 4-7/8”
Width: 4-7/8”
Depth: 7/8”
For indoor use only
Page view 0
1 2 3 4

Summary of Contents

Page 1 - Instructions

P/N 151193 I56-3546-000SD500-SDM InstallationInstructionsThe SD500-SDM two-wire smoke module allows you to connect a loop of conventional detectors t

Page 2 - Two-Wire Smoke Detectors

SD500-SDM Installation Instructions2 P/N 151193(Style B) supervision position (see Figure 4).Figure 2: Class B (Style B) 2-Wire Detector LoopNote: Aux

Page 3

SD500-SDM Installation InstructionsP/N 151193 3Note: The maximum number of smoke detectors per zone is determined by both the current draw and the imp

Page 4

SD500-SDM Installation Instructions4 151193 Rev E I56-3546-000Hochiki SIH-24F (HS-224D OR HSD-224)HD-3 HB-5 25 / loopSLK-24F (HS-224D) HD-3 HB-5 25 /

Comments to this Manuals

No comments